蓄電池在線監測系統可以(yi)監測(ce)的(de)數據有(you):電(dian)(dian)池組(zu)充放電(dian)(dian)狀態(tai)、總電(dian)(dian)壓(ya)(ya)、電(dian)(dian)流、環境溫度,以(yi)及(ji)各單(dan)體電(dian)(dian)池電(dian)(dian)壓(ya)(ya)、內阻(zu)、極(ji)柱溫度、漏液情況、膨脹變形、SOC、SOH等(deng)等(deng);但是(shi)為(wei)什么要說內阻(zu)才是(shi)蓄電(dian)(dian)池在線監測(ce)的(de)核心?
1、經過(guo)上千次的測試,我們發現蓄電池如果出現漏液、硫(liu)化、失水、變形(xing)等問(wen)題之后,內阻都會增大(da);
2、用電(dian)(dian)壓來做衡量標準,只(zhi)能(neng)找出落(luo)后(hou)(hou)電(dian)(dian)池(chi)(chi),并不是(shi)(shi)故(gu)障電(dian)(dian)池(chi)(chi);落(luo)后(hou)(hou)電(dian)(dian)池(chi)(chi)就(jiu)是(shi)(shi)在(zai)電(dian)(dian)池(chi)(chi)組其他電(dian)(dian)池(chi)(chi)都充(chong)(chong)滿電(dian)(dian)后(hou)(hou)只(zhi)有它自己還處于(yu)未充(chong)(chong)滿狀態的(de)電(dian)(dian)池(chi)(chi);這種(zhong)時候如果給落(luo)后(hou)(hou)電(dian)(dian)池(chi)(chi)進行小電(dian)(dian)流充(chong)(chong)電(dian)(dian)是(shi)(shi)可以(yi)改善(shan)到(dao)正常水平的(de);
3、用溫(wen)(wen)度來做衡量標準,因為落后電池(chi)充放電升溫(wen)(wen)比較快,故此(ci)通(tong)過溫(wen)(wen)度也很難找出(chu)故障(zhang)電池(chi);
所以說只有電池內阻才是蓄電池在線監測判別故障電(dian)池(chi)的(de)核心,內阻(zu)超過(guo)基值(新電(dian)池(chi)內阻(zu))1.5倍時請及時根(gen)據系統提示更換電(dian)池(chi)。
保定鈺鑫電氣科技有限公司專注蓄電池監測類產品的質量和研發,通過與華北電力大學、河北大學等科研院所的合作,專注產品的質量、拓寬產品應用范圍,研發出適合不同領域、不同環境的蓄電池在線監測系統,從而滿足用戶的個性化定制需求。如果貴公司想定制蓄電池監測接入方案,歡迎點擊客服(fu)或電話咨詢。
鈺鑫電(dian)氣,源(yuan)頭廠家(jia),品質穩定可靠
咨詢熱線:0312-5901192
掃描二維碼
關注微信公眾號
獲得更多(duo)資料
本文標簽: 蓄電池在線監測系統 蓄電池在線監測 定制蓄電池監測接入方案